results in an increase in soil moisture that can degrade the dielectric strength of the SKTM and potentially SKTM interference. Therefore, Tan Delta testing method is carried out as a predictive step to analyze the cable health condition and an early method to determine the good/bad of the test cable. After testing tan delta, it was obtained that the acquisition of segment 1 data results were in good condition because the average value of delta tan in all three phases was 1.0, with the differential results being 0.0 and deviation standard 0.0