Analysis of the Influence of Load Unbalance on the Neutral Current Power Loss in Substation KP10 PT. PLN (Persero) UP3 Teluk Naga

Main Article Content

Dwi Listiawati
Pawenary
Apsari Nita Andini

Abstract

The research objective is to analyze the percentage value of load unbalance before and after load balancing and the effect on neutral current losses. The load imbalance that occurs at the KP10 substation is simulated through the ETAP 16.0.0 software. Based on the research results, it was found that there was an imbalance in the load of the KP10 substation in direction B, which experienced the greatest load imbalance with a percentage of 38.76% and in direction A, which experienced a load imbalance of 19.6%. Based on SPLN No. 017 of 2014, the percentage of load imbalance exceeding 25% must be repaired. So that the repair is carried out by equalizing the load by breaking the load from direction B to direction A. After the activity of equalizing the load distribution, a decrease in the percentage of load imbalance is obtained. Majoring A is 8.9% and majoring B is 12,6%. The existence of this load imbalance also causes losses due to neutral currents where before the equalization activities the neutral current losses amounted to 6.99% and after the equalization of 1.06%. A simulation was also carried out where the load imbalance simulation results were obtained with the measurement results having results that were not much different.

Article Details

How to Cite
Listiawati, D., Pawenary, & Apsari Nita Andini. (2023). Analysis of the Influence of Load Unbalance on the Neutral Current Power Loss in Substation KP10 PT. PLN (Persero) UP3 Teluk Naga. International Journal of Advanced Multidisciplinary, 2(3), 690-702. https://doi.org/10.38035/ijam.v2i3.354
Section
Articles

References

[1] Wayan Yoga Prasetya, I., Nyoman Setiawan, I., & Gede Dyana Arjana, I. (2020). Analysis Of Load Unbalance And Harmonics In Distribution Transformer Mi 0096 Abianbase Feeder (Vol. 7, Number 1).
[2] Irsan Pasaribu, F., Sahnur Nasution, E., & Rizki, A. (2021).
The Influence Of Load Unbalance On Neutral Current And Losses In 200 Kva Distribution Transformer. Synthesis Cered National Seminar On Education And Humanities Technology, 2021, 1.
[3] Sya’roni, Z. (2019). Analisis Load Unbalance On 20 Kv Distribution Transformer And Its Solutions In Low Voltage Networks. https://ejournal.unesa.ac.id/index.php/JTE/article/view/26308/24090
[4] Latupeirissa, H. L. (2017). Pengaruh Load Unbalance On Neutral Current And Power Losses In Distribution Transformer At Substation Kp-01, Hative Kecil Village. Simetrik Journal, 7(2), 2017.
[5] Sogen, M. D. (2018). Analisis Pengaruh Load Unbalance On Neutral Current And Losses In Distribution Transformers At Pt Pln (Persero) Area Sorong.
[6] Hidayat, S., Legino, S., Fatihah Mulyanti, N., Elektro, T., Kunci, K., Tegangan Rendah, J., Distribusi, G., & Beban, P. (2018). Load Balancing In Low Voltage Networks Of Distribution Substation Cd 33 Feeder Sawah At Pt Pln (Persero) Bintaro Area. In Journal Sutet (Vol. 8, Issue) http://jurnal.itpln.ac.id/sutet/article/view/712